Advocacy
September 4, 2024 | 7 minute read

The Refrigerant Management Program (RMP) is a regulatory requirement affecting distributors and users of refrigerants. RMP has two major components: recordkeeping & reporting and leak detection & repair. RMP requires recordkeeping and reporting by both distributors and users of refrigerants and requires users of refrigerants with systems containing more than 50 pounds of refrigerant to conduct periodic leak detection and repair. Additionally, distributors and users of refrigerants will be required to register with Washington’s Refrigerant and Air-conditioning Management Platform.
Beginning Jan. 1, 2024, all refrigerant wholesalers, distributors, and reclaimers must maintain specific records for a minimum of 5 years. Refrigerant distributors, wholesalers, and reclaimers are required to submit an annual report to the Department of Ecology starting March 15, 2025. The annual report must cover all Washington facilities and provide contact information and refrigerant distribution data.
Reporting
Refrigerant distributors, wholesalers, and reclaimers are required to submit an annual report. The annual report is based on the company’s aggregated statewide purchases and sales and includes information on all locations in the state. The annual report must provide all of the following information:
Contact information:
Name of the refrigerant wholesaler or distributor facility;
Facility identification number as it appears in the WA RMP data reporting system;
Mailing address, including street address, city, state, and zip code;
Name of contact person;
Contact person's phone number and email address;
Name of each distributor or wholesaler facility under operational control;
Address of each distributor or wholesaler facility under operational control; and
Contact person's name, phone number, and email address for each refrigerant distributor or wholesaler facility under operational control.
Refrigerant distribution information:
Total statewide annual aggregated weight in pounds of each type of bulk refrigerant with a GWP of 150 or more purchased or received for subsequent resale or delivery and
Total statewide annual aggregated weight in pounds of each type of bulk refrigerant with a GWP of 150 or more sold or distributed to a facility in Washington.
Reporting of bulk refrigerant purchases and sales are required, refrigerant contained in pre-charged equipment is not included.
Recovered refrigerant transferred to a reclaimer is not included in the above-aggregated amounts.
Recordkeeping
Beginning Jan. 1, 2024, all refrigerant wholesalers, distributors, and reclaimers must maintain specific records for a minimum of 5 years. Records can be physical or electronic but must be kept at the facility housing the relevant systems. These records must include:
Annual reports submitted to the Department of Ecology;
Invoices of all refrigerant(s) with a GWP of 150 or more received through sale or transfer and all refrigerant(s) distributed for sale or transfer. These invoices must include all of the following information:
Name of the purchaser;
Date of sale or transfer;
Quantity sold or transferred; and
Type of refrigerant(s) with a GWP of 150 or more purchased, sold, or transferred.
A refrigerant distributor or wholesaler selling a refrigerant with a GWP of 150 or more to a purchaser who is an employer of a certified technician must obtain written documentation showing that the purchaser currently employs at least one certified technician.
The requirement to obtain written documentation is more stringent than the current recordkeeping requirement set by EPA’s 608 program.
These records must be kept at the refrigerant distributor or wholesaler's facility and made available to an authorized HFC program representative upon request.
Recordkeeping and reporting guidelines can be found in the HFC informational handbook. More information on distributor recordkeeping and reporting requirements can be found in the rule.
Facilities with refrigeration and air conditioning systems containing more than 50 pounds of refrigerant with a GWP of 150 or more to conduct and report periodic leak inspections, promptly repair leaks, and keep service records on site. The RMP is designed to reduce emissions of high-GWP refrigerants from leaky refrigeration and air-conditioning equipment and reduce emissions from installing and servicing refrigeration and air-conditioning appliances. The strategy of the program includes:
Registration
Refrigerant leak detection and monitoring
Leak repair
Recordkeeping and reporting
System retrofit or retirement planning
Required service practices
For specific requirements on recordkeeping and reporting, please refer to the rule.
Use the step-by-step user guide to walk you through the process.
Sign up for a Secure Access Washington (SAW) account. SAW is a platform used by Washington state agencies for information security. Skip this step if you already have a business account in SAW.
Sign in to your SAW account.
Add the Climate Pollution Reduction Application portal to your list of services in SAW.
Create a profile in the Climate Pollution Reduction Application portal.
Add the Refrigerant and Air Conditioning Management Program (RAMP) to your list of applications in the Climate Pollution Reduction Application portal.
Open RAMP through the Climate Pollution Reduction Application portal to submit registration materials.
Access RAMP through the Climate Pollution Reduction Application Portal and log in to complete registration.
Note: No fees for wholesalers, distributors, or reclaimers
Fees are assessed based on facility system size. Each facility must pay one fee based on the largest system at that facility.
Facilities with large refrigeration or air conditioning systems:
There is a one-time implementation fee of $150
There is an annual fee of $370
Facilities with medium refrigeration or air conditioning systems:
There is an annual fee of $170.
Facilities with small refrigeration or air conditioning systems:
There are no fees for facilities with a small system.
All fees are due and payable to Ecology within 30 days of receipt of the invoice following registration.
System Charge (lbs.) | Registration Deadline | Implementation Fee | Annual Fee |
≥ 1,500 (large) | March 15, 2024 | $150 | $370 |
200 ≤ 1,499 (medium) | March 15, 2026 | None | $170 |
50 ≤ 199 (small) | March 15, 2028 | None | None |
Any facility with a refrigeration or air conditioning system containing over 50 pounds of refrigerant with a GWP of 150 or more, a high-GWP must be regularly inspected for leaks. The frequency of inspection for each system varies by the size category of the system.
Facility Category | Leak Inspection Frequency | Effective Date |
≥ 1,500 (large) | Monthly (if automatic leak detection is not installed) - Enclosed systems required to utilize an automatic leak detection that meets specifications | January 1, 2024 |
200 ≤ 1,499 (medium) | Quarterly - None for systems with automatic leak detection that meet specifications | January 1, 2026 |
50 ≤ 199 (small) | Annually - None for systems with automatic leak detection that meet specifications | January 1, 2028 |
Systems not operated year-round (≥ 50 lbs.) | Within 30 days of resuming operation; then every 90 days or less | See above |
Monitoring leaks requirements for large systems:
Install an automatic leak detection system by Jan. 1, 2025, if the refrigerant circuit, compressor, evaporator, condenser, or other component with a high potential for leakage is fully enclosed within a building or structure.
Leak Repair
Fix all leaks within 14 days of detection
Refer to leak repair provisions if leaks cannot be fixed within 14 days
Check system for leaks after repair
Use only U.S. EPA-certified technicians
If leak repair fails, a Retrofit and Retirement Plan is required unless an exemption is granted
As a distributor in the State of Washington, your business needs to be registered for the RMP. It's crucial to inform customers about the upcoming requirements to ensure they meet certifications, undergo leak inspections, and fulfill other necessary obligations. Understanding the requirements that will affect inventory is also vital. For instance, having a timeline for repairing leaks means that it's important to have leak repair items readily available for customers. Moreover, the RMP aims to improve the state's understanding of the location of refrigerants within Washington and encourage reclamation efforts by tracking the circulation of refrigerants. Stay updated on HVACR news in Washington State on HARDI's State Issues page.
Information was gathered from the Washington State Department of Ecology site.
Contact Todd Titus, Director of State and Public Affairs, with additional questions.