The first round of reviews for proposed changes to national model codes is finally over. Over the last several weeks I have had the opportunity to represent HARDI and ASA distributor members during the review process. In this post, I am highlighting several actions taken by the model code technical committees that impact the HVAC distribution industry. The actions relate to storage requirements for the new A2L low GWP refrigerants along with actions that have a direct impact on products you might currently provide or may consider providing in the future.
As noted in a previous post, HARDI, ASA, AHRI and other industry experts worked diligently throughout 2020 in the development of proposed changes to the International Fire Code (IFC) and the International Building Code. These proposals were finalized and submitted in early January 2021 for consideration by the Code Committee. During the recent code hearings, myself along with Alex Ayers from HARDI, representatives from AHRI and technical fire experts testified in support of the proposed changes leading to the Code Committee voting in full support of the changes without modification. The following highlights the changes:
New Categories for Flammable Gas: A2L refrigerants in the gas phase are flammable but represent a low-flammability risk. The current International Fire Code definition for flammable gas provides no categories of flammability and only define the gases based on ignitability and flammability range. The proposed change to the IFC proposed new levels of flammable gases based on the 7th edition of the Global Harmonization System of Classification and Labeling of Chemicals. A2L refrigerants fall into the lower flammability category of 1B.
New Maximum Allowable Quantities for 1B Flammable Gas: Acceptance of the new category 1B flammable gas provides for the acceptance of Maximum Allowable Quantities (MAQs) for storage of the Category 1B gas that are significantly higher than the higher flammability category while still ensuring a high level of safety. Briefly, the new proposed MAQs for the storage of Category 1B gases (including A2Ls) per control area is 10,000 pounds of liquid or 162,500 cubic feet of gas. These MAQs can be increased 100% in building equipped with automatic sprinkler systems. These MAQs should allow for the storage of the A2L refrigerant gases without significant infrastructure costs based on a recent survey of HARDI members.
Special Storage Limits for Warehouse Storage: In addition to the general MAQ change, an additional proposal allows for increased storage of 1B Flammable Gas in warehouse storage. With this change distributors will be able to store 20,000 pounds of refrigerant with no changes to existing fire protection measures, and with additional changes including sprinkler density upgrades and use of separate storage of refrigerants in rooms with one hour fire barriers a distributor can store up to 160,000 pounds in a single location.
Impact on Products Distributed in the HVAC Market: proposed changes to the model codes and the action taken by the applicable technical committee have a potential impact on the following products –
Polyethylene of Raised Temperature / Aluminum / Polyethylene of Raised Temperature (PERT/AL/PERT) Line Sets: Proposals were submitted for inclusion of PERT/AL/PERT line sets into the International Mechanical Code and the Uniform Mechanical Code. The inclusion of the product was approved by the IMC Committee but was rejected by the UMC
Committee.
Refrigerant Piping Joints: the UMC Committee rejected proposals to include UL standards of compliance for press-fit fittings and accepted proposals that would only allow for brazed joints for all refrigerant joints. The current UMC allows for the use of press fitting, mechanical joints and soldering.
Refrigerant Detection Systems: The UMC accepted proposed changes based on ASHRAE standards that will require where A2L refrigerants are used, each refrigerant machinery room will be required to contain or more refrigerant detectors.
For a more detailed description of each of the proposals I have put together a small spreadsheet summarizing each proposal and a link within the spreadsheet that provides the detailed proposal submitted.
So what happens next? The following tables highlights the key steps remaining in the code development cycle for both the International Codes and the Uniform Codes. The final outcome of the process will be the adoption on revised 2024 model codes that will subsequently be adopted into state and local regulatory requirements.
The results of the ICC International Fire Code hearings were positive and it is anticipated no further action will be needed unless public comment is received in opposition to the actions taken by the technical committee.
The actions taken by the IAPMO Uniform Committee related to the prevention of sale of
specific product in the market place related to refrigerant piping and joining is concerning and I anticipate additional action will be needed. The potential removal of all joining systems in refrigerant line systems is definitely concerning. I will be working with HARDI staff to work out a game plan for submitting comments on the actions taken by the January 4, 2022 deadline.
If you have any questions about the codes process or the specific proposals supported by HARDI, feel free to reach out to HARDI Government Affairs Director, Alex Ayers.