EPA Releases Final Technology Transition Rule Limiting Refrigerants Used in Future Equipment

October 10, 2023 | 12 minute read

The Environmental Protection Agency (EPA) has finalized its technology transition rule, which limits the GWP of refrigerants used in comfort cooling and refrigeration equipment. The finalized rule will prohibit manufacturing or installing most equipment using current high-GWP refrigerants as early as January 1, 2025, depending on the sector and sub-sector and if the equipment is considered a product or a system. EPA has made it clear that repairs to existing systems or retrofits to change refrigerants in existing systems are not prohibited by the rule. This means parts and components for repair/retrofit can still be manufactured and sold past the compliance deadline.

The EPA released the pre-publication version of the rule on October 6, 2023, and changes can potentially be made to the rule before its publication in the Federal Register. Unfortunately, changes made to the rule between its proposal and final versions have created confusion about how many products are treated in determining its compliance date. EPA created two categories of equipment, products and systems, each with its compliance regime. The final rule defines the two categories:

  • Product means an item or category of items manufactured from raw or recycled materials which performs a function or task and is functional upon completion of manufacturing. The term includes, but is not limited to: appliances, foams, fully formulated polyols, self-contained fire suppression devices, aerosols, pressurized dispensers, and wipes.

  • System means an assemblage of separate components that typically are connected and charged in the field with a regulated substance or substitute to perform a function or task.

Equipment qualifying as a product has a manufacturing prohibition with a three-year sell-through on remaining inventory. Equipment qualifying as a system has an install date prohibition. The manufacturing and installation prohibitions fall on the same date for all sectors and sub-sectors. For example, a window air conditioner using a high-GWP refrigerant cannot be manufactured after January 1, 2025, and a split-system air conditioner using a high-GWP refrigerant cannot be installed after January 1, 2025.

This two-definition regulation creates inconsistency for HVACR equipment. The background text described the restriction on products that are self-contained, a term not in the regulatory definitions, to be a January 1, 2025, manufacturing prohibition and a three-year sell-through. This means a package air conditioner, which is functional upon completion of manufacturing, is a product. In contrast, a split-system air conditioner, which requires an installer to complete the refrigerant circuit, is considered a system and must be installed before January 1, 2025. This means the two pieces of equipment, while very similar in function, face two very different regulatory regimes.

EPA also provided two additional definitions that further confuse the intent of the regulation:

  • Manufacture means to complete the manufacturing and assembly processes of a product or specified component such that it is ready for initial sale, distribution, or operation.

  • Install means to complete a field-assembled system’s circuit, including charging with a full charge, such that the system can function and is ready for use for its intended purpose.

From reading the explanation of the final rule, each definition supports one of the two categories: manufacture aligning with products and install aligning with systems. A manufactured product is ready for operation when it leaves the factory and installed products require expert installation before operation. But, again, products like package units and split systems are cast into very different regulatory regimes despite being very similar products.

In addition to the confusion created by the two categories, HARDI is also disappointed any part of the rule comes with an install date requirement. HARDI pushed for using manufacture date compliance on all products to ensure distribution can deplete its inventory of all remaining systems. Even the three-year sell-through provided by EPA goes against the fundamental principle that distribution should not be forced to discard functional equipment because of a regulatory regime.

Another concerning component of the final rule is an export ban on products manufactured to use high-GWP refrigerants. While the U.S. is moving forward with its transition, Canada and Mexico are moving on slower timelines. The export ban will impact U.S. manufacturers who are unable to export products past the compliance deadline and hurt distributors working in Canada and Mexico because they will be unable to move products from the U.S. after the compliance date. The final rule allows the continued export of components, including condensing and evaporator units.

The GWP limits set by the final rule align with the industry petition and proposed rule, with comfort cooling having a GWP limit of 700 and commercial refrigeration having a limit of 700, 300, or 150, depending on the end-use. HARDI joined several others in the industry in requesting a later compliance date for commercial refrigeration because the SNAP program has not yet approved the replacement refrigerants and the final rule moved back the compliance deadline for most of these products.

The below tables show the compliance deadline for products and systems, remember, “unitary systems” are listed in the systems table. Note: Any equipment in existence before December 27, 2020, is exempt from these compliance deadlines.

Self-contained Refrigeration, Air Conditioning, and Heat Pumps – Restricted Products by Sector and Subsector Table*

(MVAC and Refrigerated Transport Subsectors available at EPA website)

Subsector

Product

Global Warming Potential Limit or Prohibited Substances

Manufacture and Import Compliance Date(1)

Stationary residential and light commercial air conditioning and heat pumps (e.g., window units, portable room air conditioning)

Stationary residential and light commercial air conditioning and heat pumps (e.g., window units, portable room air conditioning)

700

January 1, 2025

Residential dehumidifiers

Residential dehumidifiers

700

January 1, 2025

Household refrigerators and freezers

Household refrigerators and freezers

150

January 1, 2025

Vending machines

Vending machines

150

January 1, 2025

Chillers (as a stand-alone product)

Industrial process refrigeration with exiting fluid below -50 °C (-58 °F)

Not covered

Not covered

Chillers (as a stand-alone product)

Industrial process refrigeration with exiting fluid greater than or equal to -50 °C (-58 °F) and less than -30 °C (-22 °F)

700

January 1, 2028

Chillers (as a stand-alone product)

Industrial process refrigeration with exiting fluid equal to or above -30 °C (-22 °F)

700

January 1, 2026

Chillers (as a stand-alone product)

Comfort cooling

700

January 1, 2025

Chillers (as a stand-alone product)

Ice rinks

700

January 1, 2025

Data centers, computer room air conditioning, and information technology equipment cooling

Data centers, computer room air conditioning, and information technology equipment cooling

700

January 1, 2027

Industrial process refrigeration (not using chillers)

With refrigerant entering the evaporator below -50 °C (-58 °F)

Not covered

Not covered

Industrial process refrigeration (not using chillers)

With refrigerant entering the evaporator equal to or above -50 °C (-58 °F) and less than -30 °C (-22 °F)

700

January 1, 2028

Industrial process refrigeration (not using chillers)

High temperature side of cascade system and temperature of the refrigerant entering the evaporator equal to or above -30 °C (-22 °F)

300

January 1, 2026

Industrial process refrigeration (not using chillers)

With less than 200 lb refrigerant charge and temperature of the refrigerant entering the evaporator equal to or above -30 °C (-22 °F)

300

January 1, 2026

Industrial process refrigeration (not using chillers)

With 200 or more lb refrigerant charge excluding high temperature side of cascade system and temperature of the refrigerant entering the evaporator equal to or above -30 °C (-22 °F)

150

January 1, 2026

Retail food - refrigeration stand-alone units

Retail food - refrigeration stand-alone units

150

January 1, 2025

Retail food - refrigerated food processing and dispensing equipment

500 g of refrigerant or less and outside scope of UL 621, edition 7

150

January 1, 2027

Retail food - refrigerated food processing and dispensing equipment

More than 500 g of refrigerant and outside scope of UL 621, edition 7

R-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-407F, R-407H, R-408A, R-410A, R-410B, R-411A, R-411B, R-417A, R-417C, R-420A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-427A, R-428A, R-434A, R-437A, R-438A, R-507A, HFC-134a, HFC-227ea, R-125/290/134a/600a (55/1/42.5/1.5), RB-276, RS-24 (2002 formulation), RS-44 (2003 formulation), GHG-X5, Freeze 12

January 1, 2027

Retail food - refrigerated food processing and dispensing equipment

Ice cream makers within the scope of UL 621, edition 7

R-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-407F, R-407H, R-408A, R-410A, R-410B, R-411A, R-411B, R-417A, R-417C, R-420A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-427A, R-428A, R-434A, R-437A, R-438A, R-507A, HFC-134a, HFC-227ea, R-125/290/134a/600a (55/1/42.5/1.5), RB-276, RS-24 (2002 formulation), RS-44 (2003 formulation), GHG-X5, Freeze 12

January 1, 2028

Self-contained automatic commercial ice machines

Batch type: harvest rate <=1,000 lb ice per 24 hours

150

January 1, 2026

Self-contained automatic commercial ice machines

Continuous type: harvest rate <=1,200 lb ice per 24 hours

150

January 1, 2026

Self-contained automatic commercial ice machines

Batch type: harvest rate above 1,000 lb ice per 24 hours

R-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-407F, R-408A, R-410A, R-410B, R-411A, R-411B, R-417A, R-417C, R-420A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-428A, R-434A, R-437A, R-438A, R-442A, R-507, R-507A, HFC-134a, R-125/290/134a/600a (55/1/42.5/1.5), RB-276, RS-24 (2002 formulation), RS-44 (2003 formulation), GHG-X5, G2018C, Freeze 12

January 1, 2027

Self-contained automatic commercial ice machines

Continuous type: harvest rate above 1,200 lb ice per 24 hours

R-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-407F, R-408A, R-410A, R-410B, R-411A, R-411B, R-417A, R-417C, R-420A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-428A, R-434A, R-437A, R-438A, R-442A, R-507, R-507A, HFC-134a, R-125/290/134a/600a (55/1/42.5/1.5), RB-276, RS-24 (2002 formulation), RS-44 (2003 formulation), GHG-X5, G2018C, Freeze 12

January 1, 2027

Cold storage warehouses

With 200 or more lb refrigerant charge, excluding high temperature side of cascade system

150

January 1, 2026

Cold storage warehouses

With less than 200 lb refrigerant charge

300

January 1, 2026

Cold storage warehouses

High temperature side of cascade system

300

January 1, 2026

*These tables are for informational purposes only and should not be relied on for compliance purposes. Please refer to 40 CFR Part 82, Subpart B for full details.

(1) Sale, distribution, and export of these products is prohibited three years after the manufacture and import compliance date.

Refrigeration, Air Conditioning, and Heat Pumps – Restricted Systems by Sector and Subsector Table*

(Refrigerated Transport Subsectors available at EPA website)

Subsector

System

Global Warming Potential Limit or Prohibited Substances

Installation Compliance Date(5)

Stationary residential and light commercial air conditioning and heat pumps

Residential and light commercial air conditioning and heat pump systems (e.g., mini-splits, unitary systems)

700

January 1, 2025

Stationary air conditioning and heat pumps

Variable refrigerant flow systems

700

January 1, 2026

Chillers

Industrial process refrigeration with exiting fluid below -50 °C (-58 °F)

Not covered

Not covered

Chillers

Industrial process refrigeration with exiting fluid from -50 °C (-58 °F) to -30 °C (-22 °F)

700

January 1, 2028

Chillers

Industrial process refrigeration with exiting fluid above -30 °C (-22 °F)

700

January 1, 2026

Chillers

Comfort cooling

700

January 1, 2025

Ice rinks

Ice rinks

700

January 1, 2025

Data centers, computer room air conditioning, and information technology equipment cooling

Data centers, computer room air conditioning, and information technology equipment cooling

700

January 1, 2027

Industrial process refrigeration (not using chillers)

With 200 or more lb refrigerant charge excluding high temperature side of cascade system and temperature of the refrigerant entering the evaporator above -30 °C (-22 °F)

150

January 1, 2026

Industrial process refrigeration (not using chillers)

With less than 200 lb refrigerant charge and temperature of the refrigerant entering the evaporator above -30 °C (-22 °F)

300

January 1, 2026

Industrial process refrigeration (not using chillers)

High temperature side of cascade systems and temperature of the refrigerant entering the evaporator above -30 °C (-22 °F)

300

January 1, 2026

Industrial process refrigeration (not using chillers)

Temperature of the refrigerant entering the evaporator from -50 °C (-58 °F) to -30 °C (-22 °F)

700

January 1, 2028

Industrial process refrigeration (not using chillers)

Temperature of the refrigerant entering the evaporator below -50 °C (-58 °F)

Not covered

Not covered

Cold storage warehouses

With 200 or more lb refrigerant charge, excluding high temperature side of cascade system

150

January 1, 2026

Cold storage warehouses

With less than 200 lb refrigerant charge

300

January 1, 2026

Cold storage warehouses

High temperature side of cascade system

300

January 1, 2026

Retail food - supermarkets

With 200 or more lb refrigerant charge, excluding high temperature side of cascade system

150

January 1, 2027

Retail food - supermarkets

With less than 200 lb refrigerant charge

300

January 1, 2027

Retail food - supermarkets

High temperature side of cascade systems

300

January 1, 2027

Retail food - remote condensing units

With 200 or more lb refrigerant charge, excluding high temperature side of cascade system

150

January 1, 2026

Retail food - remote condensing units

With less than 200 lb refrigerant charge

300

January 1, 2026

Retail food - remote condensing units

High temperature side of cascade system

300

January 1, 2026

Retail food - remote refrigerated food processing and dispensing equipment

Retail food - remote refrigerated food processing and dispensing equipment

R-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-407F, R-407H, R-408A, R-410A, R-410B, R-411A, R-411B, R-417A, R-417C, R-420A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-427A, R-428A, R-434A, R-437A, R-438A, R-507A, HFC-134a, HFC-227ea, R-125/290/134a/600a (55/1/42.5/1.5), RB-276, RS-24 (2002 formulation), RS-44 (2003 formulation), GHG-X5, Freeze 12

January 1, 2027

Remote automatic commercial ice machines

Remote automatic commercial ice machines

R-402A, R-402B, R-404A, R-407B, R-408A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-428A, R-434A, R-438A, R-507A, R-125/290/134a/600a (55/1/42.5/1.5), RS-44 (2003 formulation), GHG-X5

January 1, 2027

*These tables are for informational purposes only and should not be relied on for compliance purposes. Please refer to 40 CFR Part 82, Subpart B for full details.

(5) EPA is restricting the installation of new field-assembled systems. Components used to repair existing systems are not subject to these restrictions.

Alex Ayers
Vice President of Government Affairs
Alex is HARDI’s lead lobbyist and regulatory expert, with over a decade of experience in Washington, DC. A former Iowa caucus delegate, he built early roots in grassroots politics. He has lobbied, published, and testified on taxes, energy, environment, agriculture, and economics. His work has been cited by the Wall Street Journal, Forbes, and the Tax Foundation.