I recently attended the second round of meetings to discuss proposed changes to the International Association of Plumbing and Mechanical Officials (IAPMO) Uniform Mechanical Code (UMC). The UMC is considered for adoption into regulation by state and local government agencies across the U.S. Currently, on a state adoption basis, the UMC has been adopted in CA, NV, and NM. The following are key results from the hearings:
A2L Refrigerants: Through the combined efforts of several trade organizations including HARDI, ASA, AHRI, ASHRAE, and others, the UMC Technical Committee (TC) reversed its rejection of the incorporation of A2L refrigerant requirements and preliminarily approved one of two proposals submitted by the industry. These changes are critical for providing code guidance on the implementation of regulatory requirements related to greenhouse gas emission and changing to low greenhouse gas emitting refrigerants. The proposal received greater than a 2/3 affirmative vote.
Refrigerant Line Joints: A proposal to accept an amended version of the industry proposal related to A2Ls with a requirement that only brazed joints could be used was rejected. Unfortunately, another proposal requiring “all joints on refrigeration piping installed in concealed spaces shall be brazed” was accepted by the TC by a slim majority; but will require a 2/3 affirmative vote in the letter ballot process to continue forward. If adopted, the fact that a significant amount of refrigeration piping is installed in concealed spaces, the change could lead a significant reduction in the use of alternate types of joining systems currently on the market and being used without any known safety or performance issues.
The next steps in the UMC revision process will be a letter ballot sent out to the TC members. A change to the current UMC will require a 2/3 affirmative ballot of the Technical Committee. Following the balloting process, IAPMO will publish the results of the TC votes in mid-August followed by a review of items of interest from the IAPMO membership presented at the Technical Membership meeting being held on September 13, 2022 during the IAPMO Annual Meeting being held in Charlotte, NC. I will be present at the meeting representing HARDI as well as ASA. Ultimately, the final proposals accepted at the completion of the process will be incorporated into the 2024 version of the model codes for consideration of adoption by state and local authorities.
In addition to the above, HARDI has been working closely with other trade associations in opposing a proposal to remove the use of press-connect fittings from the past two published versions of the UMC by removing reference to UL 207, the national standard for refrigeration fittings. The full review process of the proposal has been completed and the IAPMO Board of Directors announced on May 22, 2022 the rejection of the proponents appeal and the Board supported the Standards Council decision to reject the proposed changes. This is the final step in the process and our opposition to the proposals has been fully upheld.
The State of Louisiana uses the International Mechanical Code (IMC) as its State Code and are in the process of considering the adoption of the 2021 edition of the IMC. We have been actively involved in the process and opposing a proposal to not adopt the acceptance of press-connect fittings for refrigeration systems based on compliance with UL 207 as currently allowed in the IMC 2021 and instead, adopt requirements that would not be consistent with UL 207 and ultimately, impacting the ability to distribute press-connect fittings for use in refrigeration systems in the State. The LA State Uniform Construction Code Council recently reviewed the issue and asked that the task group that submitted the proposal work with industry representatives and the standards developer, UL, to resolve the issue. We continue to work on this issue which needs to be resolved by the end of the year.
ASHRAE 15.2 has been published. ASHRAE 15.2 is a safety standard designed to accommodate the use of A2L-classified refrigerants in low-rise residential applications and is intended for use by manufacturers, installers, contractors, service technicians, building code officials, and others.
Standard 15.2 requires that all products be listed to a national product safety standard and installed per the manufacturer’s installation instructions. Specific requirements are included for which refrigerants can be used, the maximum allowable refrigerant charge, accessories, and interconnecting piping, so that in the event of a full release of the refrigerant charge, the concentration in the space remains safely below the lower flammability limit of the refrigerant. To learn more about the standard click here.